    SCFM to ACFM Calculator

    To convert SCFM to ACFM, multiply by (T_actual ÷ T_std) × (P_std ÷ P_actual) using absolute values: 100 SCFM of air compressed to 100 psig at 68 °F is 12.82 ACFM.

    Convert:
    Pressure is:
    Local atmospheric pressure:
    Actual flow:

    12.81649453 ACFM

    100 SCFM × 0.1281649453 = 12.81649453 ACFM

    How this was calculated:

    • T_ref = 293.15 K, P_ref = 101.3529322 kPa (absolute)
    • T_actual = 293.15 K, P_actual = 790.8007293 kPa (absolute = gauge + 101.325 kPa atmospheric)
    • Q_actual = Q_standard × (T_actual ÷ T_ref) × (P_ref ÷ P_actual), so 1 standard volume = 0.1281649453 actual volumes
    Actual flow in other units
    UnitValue
    cubic meter per second [m³/s]0.006048711824 m³/s
    cubic meter per hour [m³/h]21.77536257 m³/h
    liter per second [L/s]6.048711824 L/s
    liter per minute [L/min]362.9227094 L/min
    cubic centimeter per second [cm³/s]6048.711824 cm³/s
    cubic centimeter per minute [cm³/min]362922.7094 cm³/min
    cubic foot per minute [CFM]12.81649453 CFM
    US gallon per minute [GPM]95.874037 GPM

    SCFM to ACFM Formula

    Q_actual = Q_std × (T_actual ÷ T_std) × (P_std ÷ P_actual)

    T in kelvin or °R (absolute); P absolute (gauge + atmospheric)

    Q_std = Q_actual × (T_std ÷ T_actual) × (P_actual ÷ P_std)

    It follows from the ideal gas law, PV = nRT. A standard flow fixes the number of molecules per minute; the actual volume they occupy scales with absolute temperature and inversely with absolute pressure.

    Worked Examples

    1. Compressed air. 100 SCFM at 100 psig and 68 °F at sea level: P_actual = 114.7 psia, so Q = 100 × 14.7 ÷ 114.7 = 12.82 ACFM.
    2. Fan at altitude. 1000 SCFM at 5000 ft (barometric pressure 12.23 psia) and 68 °F: Q = 1202 ACFM; the fan must move about 120 % of the sea-level volume.
    3. Hot exhaust. 1000 ACFM at 300 °F and atmospheric pressure: Q_std = 1000 × (527.67 ÷ 759.67) × (14.696 ÷ 14.7) = 694.4 SCFM.

    Standard Reference Conditions

    Common definitions of "standard" and "normal" gas volume
    ReferenceTemperaturePressure (absolute)Note
    Standard air, 68 °F and 14.7 psia 20 °C = 68 °F 101.353 kPa = 14.7 psia 68 °F, 14.7 psia; the 36 % RH of the full definition is not modelled.
    Normal, 0 °C and 101.325 kPa 0 °C = 32 °F 101.325 kPa = 14.696 psia Normal cubic metres (Nm³), also SEMI E12 for sccm and SLPM.
    20 °C and 100 kPa 20 °C = 68 °F 100 kPa = 14.504 psia ISO 1217 standard inlet conditions: 1 bar(a), 20 °C, dry air.
    15 °C and 101.325 kPa 15 °C = 59 °F 101.325 kPa = 14.696 psia Standard reference conditions for natural gas.
    60 °F and 14.696 psia 15.556 °C = 60 °F 101.325 kPa = 14.696 psia 60 °F with one standard atmosphere.
    20 °C and 101.325 kPa 20 °C = 68 °F 101.325 kPa = 14.696 psia Often called NTP in HVAC and laboratory work.

    SCFM, ACFM, ICFM and Nm³/h

    • SCFM: standard cubic feet per minute, a mass-like flow referenced to fixed conditions.
    • ACFM: actual cubic feet per minute at the real temperature and pressure in the line or at the fan.
    • ICFM: inlet cubic feet per minute, actual flow measured at a compressor inlet (after filters).
    • Nm³/h: normal cubic metres per hour, referenced to 0 °C and 101.325 kPa (DIN 1343).
    • sccm / SLPM: standard flows used by mass flow controllers; see sccm to SLPM.

    Frequently asked questions

    What is the difference between SCFM and ACFM?

    SCFM (standard cubic feet per minute) is the flow the gas would have at a fixed reference temperature and pressure, so it measures the amount of gas. ACFM (actual cubic feet per minute) is the volume the gas really occupies at its current temperature and pressure.

    How do I convert SCFM to ACFM?

    Multiply by (T_actual ÷ T_std) × (P_std ÷ P_actual), with absolute temperatures and pressures. For 100 SCFM compressed to 100 psig at 68 °F: 100 × (14.7 ÷ 114.7) = 12.82 ACFM.

    Is ACFM always larger than SCFM?

    No. Above atmospheric pressure the gas is compressed, so ACFM is smaller than SCFM (compressed-air lines). At high temperature, low pressure or high altitude ACFM is larger (fans, exhausts, mountain sites).

    Which standard conditions should I use?

    Use the one in the specification you are matching. Compressed-air ratings in the US usually use 68 °F and 14.7 psia (CAGI), compressor tests use ISO 1217 (20 °C, 1 bar), normal cubic metres (Nm³) use 0 °C and 101.325 kPa, and the gas industry often uses 60 °F.

    How do I convert SCFM to Nm³/h?

    The references differ (68 °F and 14.7 psia vs 0 °C and 101.325 kPa), so it is more than a unit conversion: 1 SCFM ≈ 1.584 Nm³/h, not 1.699 m³/h.

    Does this include humidity or compressibility?

    No. It assumes a dry ideal gas (compressibility Z = 1), which is accurate for air at normal pressures. For humid air or high-pressure gases, apply a water-vapour or Z-factor correction.