    Induction Motor Slip Calculator

    A 4-pole, 50 Hz motor at 1440 rpm runs at a slip of 4 %: the synchronous speed is 1500 rpm and rotor currents alternate at 2 Hz.

    Power crossing to the rotor; 0 to skip the power split.

    Slip s =

    4 %

    Synchronous speed Nₛ = 120f/P
    1500 rpm
    Slip speed Nₛ − N
    60 rpm
    Rotor current frequency sf
    2 Hz
    Rotor copper loss s × P_ag
    0.4 kW
    Mechanical power (1 − s) P_ag
    9.6 kW
    Torque P_ag ÷ ωₛ
    63.66197724 N·m
    Mode
    motoring
    Step-by-step solution
    1. Nₛ = 120f ÷ P = 120 × 50 ÷ 4 = 1500 rpm
    2. s = (Nₛ − N) ÷ Nₛ = (1500 − 1440) ÷ 1500 = 0.04
    3. Rotor frequency = s f = 2 Hz

    Induction Motor Slip Formula

    Nₛ = 120f/P, s = (Nₛ − N)/Nₛ

    rotor frequency sf; rotor copper loss = sP_ag; mechanical power = (1 − s)P_ag

    Worked Example

    A 4-pole, 50 Hz motor running at 1440 rpm with 10 kW crossing the air gap:

    1. Nₛ = 120f ÷ P = 120 × 50 ÷ 4 = 1500 rpm
    2. s = (Nₛ − N) ÷ Nₛ = (1500 − 1440) ÷ 1500 = 0.04
    3. Rotor frequency = s f = 2 Hz

    Slip speed Nₛ − N: 60 rpm · Rotor current frequency sf: 2 Hz · Rotor copper loss s × P_ag: 0.4 kW · Mechanical power (1 − s) P_ag: 9.6 kW · Torque P_ag ÷ ωₛ: 63.66197724 N·m · Mode: motoring

    GATE tip

    Maximum torque occurs at slip s = R₂/X₂ and does not depend on rotor resistance in value, only in position. Starting torque is maximum when R₂ = X₂.

    More Electrical Machines Calculators

    • Transformer Calculator

      η = xS cos φ / (xS cos φ + Pᵢ + x²P_cu)

      x load fraction, Pᵢ core loss, P_cu full-load copper loss; maximum η at x = √(Pᵢ/P_cu)

      Example: A 100 kVA, 11 kV/415 V transformer with 500 W core loss and 1500 W full-load copper loss, at 75 % load and 0.8 power factor: Efficiency η = 97.8095 %.

      Open the transformer calculator →

    • DC Machine EMF Calculator

      E = PΦZN / (60A)

      A = P for lap, 2 for wave windings; motor: E_b = V − IₐRₐ, T = E_b Iₐ/ω

      Example: A 4-pole lap-wound machine with 20 mWb per pole and 500 conductors at 1200 rpm: Generated EMF E = 200 V.

      Open the dc machine emf calculator →

    Frequently asked questions

    Why can an induction motor never reach synchronous speed?

    At Nₛ the rotor sees no changing flux, so no current is induced and no torque is produced. Some slip is always needed to carry load.

    What is the power split?

    Of the air-gap power P_ag, a fraction s is lost as rotor copper loss and (1 − s) becomes mechanical power: P_ag : P_cu2 : P_mech = 1 : s : (1 − s).

    Sources

    Last reviewed: . Factors are stored exactly and computed with 50-digit decimal arithmetic. See how we verify conversion factors.

    Cite this page

    APA

    Scientific Converters. (2026, October 15). Induction Motor Slip Calculator. Retrieved October 25, 2026, from https://scientificconverters.com/calculators/induction-motor-calculator/

    IEEE

    Scientific Converters, "Induction Motor Slip Calculator," scientificconverters.com. Accessed: Oct. 25, 2026. [Online]. Available: https://scientificconverters.com/calculators/induction-motor-calculator/

    Send feedback

    Found a wrong value, a missing unit or an idea? Tell us. We read every message.

    What is it about?

    We store your message, the page you were on and your email if given. See the privacy policy.