    Thermistor Calculator

    A 10 kΩ NTC thermistor with B = 3950 K reads about 33.6206 kΩ at 0 °C, from the beta equation.

    Convert:
    Resistance R =

    33.6206037214357 kΩ

    Full answer, then cut to fewer decimals (not rounded):

    • 33.6206037214357 kΩ
    • 33.620603721435 kΩ
    • 33.62060372143 kΩ
    • 33.6206037214 kΩ
    • 33.620603721 kΩ
    • 33.62060372 kΩ
    • 33.6206037 kΩ
    • 33.620603 kΩ
    • 33.62060 kΩ
    • 33.6206 kΩ
    • 33.620 kΩ
    • 33.62 kΩ
    • 33.6 kΩ
    In ohms
    33620.60372 Ω
    Temperature coefficient −B/T²
    -5.29413103 %/K
    Step-by-step solution
    1. R = R₀ exp[B(1/T − 1/T₀)], T in kelvin
    2. R = 10000 × exp[3950 × (1/273.15 − 1/298.15)]
    3. R = 33620.60372 Ω

    Thermistor Formula

    R = R₀ exp[B(1/T − 1/T₀)]

    T in kelvin; inverse 1/T = 1/T₀ + ln(R/R₀)/B

    Worked Example

    A 10 kΩ (at 25 °C) NTC thermistor with B = 3950 K at 0 °C:

    1. R = R₀ exp[B(1/T − 1/T₀)], T in kelvin
    2. R = 10000 × exp[3950 × (1/273.15 − 1/298.15)]
    3. R = 33620.60372 Ω

    Temperature coefficient −B/T²: -5.29413103 %/K

    GATE tip

    Thermistors are very non-linear but very sensitive; RTDs are nearly linear and stable; thermocouples need no excitation and reach high temperatures. Matching sensor to requirement is a common conceptual question.

    More Sensors and Industrial Instrumentation Calculators

    • RTD Calculator

      R = R₀(1 + AT + BT²) for T ≥ 0 °C

      A = 3.9083 × 10⁻³, B = −5.775 × 10⁻⁷; below 0 °C add C(T − 100)T³, C = −4.183 × 10⁻¹²

      Example: A Pt100 at 100 °C: Resistance R = 138.5055 Ω.

      Open the rtd calculator →

    • Strain Gauge Calculator

      ΔR/R = GF × ε

      quarter bridge Vₒ ≈ V_ex GF ε / 4; half (bending) V_ex GF ε/2; full V_ex GF ε

      Example: A 350 Ω gauge, GF = 2, at 1000 µε in a quarter bridge with 5 V excitation: Bridge output Vₒᵤₜ = 2.4975 mV.

      Open the strain gauge calculator →

    • 4-20 mA Calculator

      I = 4 + 16 (PV − LRV)/(URV − LRV)

      PV = LRV + (I − 4)/16 × (URV − LRV); 250 Ω converts 4–20 mA to 1–5 V

      Example: A 0–10 bar pressure transmitter reading 2.5 bar: Loop current = 8 mA.

      Open the 4-20 ma calculator →

    Frequently asked questions

    How accurate is the beta model?

    Within about ±0.5 °C over 0–50 °C for most parts; over wider ranges use the Steinhart–Hart equation with three coefficients.

    Why is the temperature coefficient negative?

    In NTC thermistors, more carriers are freed as temperature rises, lowering resistance by roughly 4 % per kelvin near room temperature.

    Sources

    Last reviewed: . Factors are stored exactly and computed with 50-digit decimal arithmetic. See how we verify conversion factors.

    Cite this page

    APA

    Scientific Converters. (2026, October 15). Thermistor Calculator. Retrieved October 25, 2026, from https://scientificconverters.com/calculators/thermistor-calculator/

    IEEE

    Scientific Converters, "Thermistor Calculator," scientificconverters.com. Accessed: Oct. 25, 2026. [Online]. Available: https://scientificconverters.com/calculators/thermistor-calculator/

    Send feedback

    Found a wrong value, a missing unit or an idea? Tell us. We read every message.

    What is it about?

    We store your message, the page you were on and your email if given. See the privacy policy.