    Power Factor Correction Calculator

    Raising a 100 kW load from 0.7 to 0.95 power factor needs 69.152 kVAR of capacitors, cutting the line current by about 26 %.

    Supply:
    Capacitor rating Q_C =

    69.1519956041544 kVAR

    Full answer, then cut to fewer decimals (not rounded):

    • 69.1519956041544 kVAR
    • 69.151995604154 kVAR
    • 69.15199560415 kVAR
    • 69.1519956041 kVAR
    • 69.151995604 kVAR
    • 69.15199560 kVAR
    • 69.1519956 kVAR
    • 69.151995 kVAR
    • 69.15199 kVAR
    • 69.1519 kVAR
    • 69.151 kVAR
    • 69.15 kVAR
    • 69.1 kVAR
    Capacitance per phase
    426.0272676 µF
    Reactive power before
    102.0204061 kVAR
    Reactive power after
    32.86841052 kVAR
    Apparent power before
    142.8571429 kVA
    Apparent power after
    105.2631579 kVA
    Line current reduced by
    26.31578947 %
    Step-by-step solution
    1. tan φ₁ = tan(arccos 0.7) = 1.020204061; tan φ₂ = tan(arccos 0.95) = 0.3286841052
    2. Q_C = P (tan φ₁ − tan φ₂) = 100 × (1.020204061 − 0.3286841052) = 69.1519956 kVAR
    3. Delta: C per phase = Q_C ÷ (3 × 2πf V_L²) = 426.0272676 µF

    Power Factor Correction Formula

    Q_C = P (tan φ₁ − tan φ₂)

    C = Q_C / (2πf V²) single-phase; delta bank C per phase = Q_C / (3·2πf V_L²)

    Worked Example

    A 100 kW, 415 V, 50 Hz three-phase load from 0.7 to 0.95 power factor with delta capacitors:

    1. tan φ₁ = tan(arccos 0.7) = 1.020204061; tan φ₂ = tan(arccos 0.95) = 0.3286841052
    2. Q_C = P (tan φ₁ − tan φ₂) = 100 × (1.020204061 − 0.3286841052) = 69.1519956 kVAR
    3. Delta: C per phase = Q_C ÷ (3 × 2πf V_L²) = 426.0272676 µF

    Reactive power before: 102.0204061 kVAR · Reactive power after: 32.86841052 kVAR · Apparent power before: 142.8571429 kVA · Apparent power after: 105.2631579 kVA · Line current reduced by: 26.31578947 %

    GATE tip

    Work with tan φ, not angles: tan(arccos 0.8) = 0.75 and tan(arccos 0.6) = 1.333 are worth memorising, and many GATE questions use 0.8 and 0.6.

    More Electric Circuits Calculators

    All GATE Electrical Engineering calculators →

    Frequently asked questions

    Why not correct to unity?

    The last few hundredths need a lot of extra kVAR, and over-correction at light load can make the power factor leading and raise voltages. 0.95–0.98 is the usual target.

    Star or delta capacitors?

    Delta capacitors see the full line voltage, so they need one third of the capacitance of a star bank for the same kVAR.

    Sources

    Last reviewed: . Factors are stored exactly and computed with 50-digit decimal arithmetic. See how we verify conversion factors.

    Cite this page

    APA

    Scientific Converters. (2026, October 15). Power Factor Correction Calculator. Retrieved October 25, 2026, from https://scientificconverters.com/calculators/power-factor-correction-calculator/

    IEEE

    Scientific Converters, "Power Factor Correction Calculator," scientificconverters.com. Accessed: Oct. 25, 2026. [Online]. Available: https://scientificconverters.com/calculators/power-factor-correction-calculator/

    Send feedback

    Found a wrong value, a missing unit or an idea? Tell us. We read every message.

    What is it about?

    We store your message, the page you were on and your email if given. See the privacy policy.