Transformer Calculator
A 100 kVA transformer with 500 W core and 1500 W copper loss runs at 97.8095 % efficiency at 75 % load and 0.8 power factor.
From the open-circuit test; constant at any load.
From the short-circuit test; varies with the square of the load.
97.809475292919 %
Full answer, then cut to fewer decimals (not rounded):
- 97.809475292919 %
- 97.80947529291 %
- 97.8094752929 %
- 97.809475292 %
- 97.80947529 %
- 97.8094752 %
- 97.809475 %
- 97.80947 %
- 97.8094 %
- 97.809 %
- 97.80 %
- 97.8 %
- Turns ratio N₁ : N₂
- 26.5060241
- Full-load primary current (single-phase)
- 9.090909091 A
- Full-load secondary current (single-phase)
- 240.9638554 A
- Output power at this load
- 60 kW
- Total losses at this load
- 1343.75 W
- Load for maximum efficiency √(Pᵢ/P_cu)
- 57.73502692 % of full load
- Maximum efficiency
- 97.88081812 %
Step-by-step solution
- Copper loss at x = 0.75: x²P_cu = 843.75 W
- η = xS cos φ ÷ (xS cos φ + Pᵢ + x²P_cu) = 60000 ÷ (60000 + 500 + 843.75)
- η = 97.80947529 %
Transformer Formula
η = xS cos φ / (xS cos φ + Pᵢ + x²P_cu)
x load fraction, Pᵢ core loss, P_cu full-load copper loss; maximum η at x = √(Pᵢ/P_cu)
Worked Example
A 100 kVA, 11 kV/415 V transformer with 500 W core loss and 1500 W full-load copper loss, at 75 % load and 0.8 power factor:
- Copper loss at x = 0.75: x²P_cu = 843.75 W
- η = xS cos φ ÷ (xS cos φ + Pᵢ + x²P_cu) = 60000 ÷ (60000 + 500 + 843.75)
- η = 97.80947529 %
Full-load primary current (single-phase): 9.090909091 A · Full-load secondary current (single-phase): 240.9638554 A · Output power at this load: 60 kW · Total losses at this load: 1343.75 W · Load for maximum efficiency √(Pᵢ/P_cu): 57.73502692 % of full load · Maximum efficiency: 97.88081812 %
GATE tip
All-day efficiency uses energies, not powers: core loss runs 24 h while copper loss scales with x² for each period. Add up kWh of output and losses over the day.
More Electrical Machines Calculators
-
Induction Motor Slip Calculator
Nₛ = 120f/P, s = (Nₛ − N)/Nₛ
rotor frequency sf; rotor copper loss = sP_ag; mechanical power = (1 − s)P_ag
Example: A 4-pole, 50 Hz motor running at 1440 rpm with 10 kW crossing the air gap: Slip s = 4 %.
-
DC Machine EMF Calculator
E = PΦZN / (60A)
A = P for lap, 2 for wave windings; motor: E_b = V − IₐRₐ, T = E_b Iₐ/ω
Example: A 4-pole lap-wound machine with 20 mWb per pole and 500 conductors at 1200 rpm: Generated EMF E = 200 V.
Frequently asked questions
When is a transformer most efficient?
When copper loss equals core loss: at x = √(Pᵢ/P_cu) of full load. Distribution transformers are designed to peak around 50–70 % load.
What about three-phase currents?
Use I = S/(√3 V_L). The calculator’s currents are single-phase; divide them by √3 for a three-phase unit with line voltages.
Sources
- The International System of Units (SI), 9th edition (SI Brochure), Bureau International des Poids et Mesures .
Last reviewed: . Factors are stored exactly and computed with 50-digit decimal arithmetic. See how we verify conversion factors.
Cite this page
APA
Scientific Converters. (2026, October 15). Transformer Calculator. Retrieved October 25, 2026, from https://scientificconverters.com/calculators/transformer-calculator/
IEEE
Scientific Converters, "Transformer Calculator," scientificconverters.com. Accessed: Oct. 25, 2026. [Online]. Available: https://scientificconverters.com/calculators/transformer-calculator/