    Transformer Calculator

    A 100 kVA transformer with 500 W core and 1500 W copper loss runs at 97.8095 % efficiency at 75 % load and 0.8 power factor.

    From the open-circuit test; constant at any load.

    From the short-circuit test; varies with the square of the load.

    %
    Efficiency η =

    97.809475292919 %

    Full answer, then cut to fewer decimals (not rounded):

    • 97.809475292919 %
    • 97.80947529291 %
    • 97.8094752929 %
    • 97.809475292 %
    • 97.80947529 %
    • 97.8094752 %
    • 97.809475 %
    • 97.80947 %
    • 97.8094 %
    • 97.809 %
    • 97.80 %
    • 97.8 %
    Turns ratio N₁ : N₂
    26.5060241
    Full-load primary current (single-phase)
    9.090909091 A
    Full-load secondary current (single-phase)
    240.9638554 A
    Output power at this load
    60 kW
    Total losses at this load
    1343.75 W
    Load for maximum efficiency √(Pᵢ/P_cu)
    57.73502692 % of full load
    Maximum efficiency
    97.88081812 %
    Step-by-step solution
    1. Copper loss at x = 0.75: x²P_cu = 843.75 W
    2. η = xS cos φ ÷ (xS cos φ + Pᵢ + x²P_cu) = 60000 ÷ (60000 + 500 + 843.75)
    3. η = 97.80947529 %

    Transformer Formula

    η = xS cos φ / (xS cos φ + Pᵢ + x²P_cu)

    x load fraction, Pᵢ core loss, P_cu full-load copper loss; maximum η at x = √(Pᵢ/P_cu)

    Worked Example

    A 100 kVA, 11 kV/415 V transformer with 500 W core loss and 1500 W full-load copper loss, at 75 % load and 0.8 power factor:

    1. Copper loss at x = 0.75: x²P_cu = 843.75 W
    2. η = xS cos φ ÷ (xS cos φ + Pᵢ + x²P_cu) = 60000 ÷ (60000 + 500 + 843.75)
    3. η = 97.80947529 %

    Full-load primary current (single-phase): 9.090909091 A · Full-load secondary current (single-phase): 240.9638554 A · Output power at this load: 60 kW · Total losses at this load: 1343.75 W · Load for maximum efficiency √(Pᵢ/P_cu): 57.73502692 % of full load · Maximum efficiency: 97.88081812 %

    GATE tip

    All-day efficiency uses energies, not powers: core loss runs 24 h while copper loss scales with x² for each period. Add up kWh of output and losses over the day.

    More Electrical Machines Calculators

    Frequently asked questions

    When is a transformer most efficient?

    When copper loss equals core loss: at x = √(Pᵢ/P_cu) of full load. Distribution transformers are designed to peak around 50–70 % load.

    What about three-phase currents?

    Use I = S/(√3 V_L). The calculator’s currents are single-phase; divide them by √3 for a three-phase unit with line voltages.

    Sources

    Last reviewed: . Factors are stored exactly and computed with 50-digit decimal arithmetic. See how we verify conversion factors.

    Cite this page

    APA

    Scientific Converters. (2026, October 15). Transformer Calculator. Retrieved October 25, 2026, from https://scientificconverters.com/calculators/transformer-calculator/

    IEEE

    Scientific Converters, "Transformer Calculator," scientificconverters.com. Accessed: Oct. 25, 2026. [Online]. Available: https://scientificconverters.com/calculators/transformer-calculator/

    Send feedback

    Found a wrong value, a missing unit or an idea? Tell us. We read every message.

    What is it about?

    We store your message, the page you were on and your email if given. See the privacy policy.