    The unbalanced set 100∠0°, 80∠−120°, 90∠120° has a positive-sequence component of 90 ∠ 0°, with small negative and zero sequences.

    °
    °
    °
    Positive sequence V₁ =

    90

    Negative sequence V₂
    5.7735 ∠ -30°
    Zero sequence V₀
    5.7735 ∠ 30°
    Unbalance factor |V₂|/|V₁|
    6.415002991 %
    Check V₀ + V₁ + V₂
    100 ∠ 0° (= V_a)
    Step-by-step solution
    1. a = 1∠120°, a² = 1∠240°
    2. V₀ = (V_a + V_b + V_c) ÷ 3 = 5.7735 ∠ 30°
    3. V₁ = (V_a + aV_b + a²V_c) ÷ 3 = 90 ∠ 0°
    4. V₂ = (V_a + a²V_b + aV_c) ÷ 3 = 5.7735 ∠ -30°

    Symmetrical Components Formula

    V₁ = (V_a + aV_b + a²V_c)/3

    V₀ = (V_a + V_b + V_c)/3, V₂ = (V_a + a²V_b + aV_c)/3, a = 1∠120°

    Worked Example

    Unbalanced phases V_a = 100∠0°, V_b = 80∠−120°, V_c = 90∠120°:

    1. a = 1∠120°, a² = 1∠240°
    2. V₀ = (V_a + V_b + V_c) ÷ 3 = 5.7735 ∠ 30°
    3. V₁ = (V_a + aV_b + a²V_c) ÷ 3 = 90 ∠ 0°
    4. V₂ = (V_a + a²V_b + aV_c) ÷ 3 = 5.7735 ∠ -30°

    Zero sequence V₀: 5.7735 ∠ 30° · Unbalance factor |V₂|/|V₁|: 6.415002991 % · Check V₀ + V₁ + V₂: 100 ∠ 0° (= V_a)

    GATE tip

    Remember 1 + a + a² = 0 and a³ = 1. For a balanced set V₂ = V₀ = 0; a line-to-line fault has no zero sequence; a ground fault on a delta winding cannot pass zero-sequence current.

    More Power Systems Calculators

    • Per-Unit Calculator

      Z_new = Z_old (kV_old/kV_new)² (MVA_new/MVA_old)

      Z_base = kV²/MVA; I_base = MVA/(√3 kV); fault MVA = MVA_base/Z_pu

      Example: A 0.1 pu reactance on 50 MVA, 11 kV, moved to a 100 MVA, 11 kV base: Impedance on the new base = 0.2 pu.

      Open the per-unit calculator →

    Frequently asked questions

    What do the sequences mean physically?

    Positive sequence rotates the normal way and produces useful torque; negative sequence rotates backwards and heats motors; zero sequence is in phase on all three lines and returns through neutral or earth.

    How do faults use them?

    A single line-to-ground fault connects the three sequence networks in series: I_f = 3V/(Z₁ + Z₂ + Z₀).

    Sources

    Last reviewed: . Factors are stored exactly and computed with 50-digit decimal arithmetic. See how we verify conversion factors.

    Cite this page

    APA

    Scientific Converters. (2026, October 15). Symmetrical Components Calculator. Retrieved October 25, 2026, from https://scientificconverters.com/calculators/symmetrical-components-calculator/

    IEEE

    Scientific Converters, "Symmetrical Components Calculator," scientificconverters.com. Accessed: Oct. 25, 2026. [Online]. Available: https://scientificconverters.com/calculators/symmetrical-components-calculator/

    Send feedback

    Found a wrong value, a missing unit or an idea? Tell us. We read every message.