Lumen Method Calculator
A 10 × 8 m office lit to 300 lux with twin-lamp 3000 lm luminaires (UF 0.6, MF 0.8) needs 8.33333 luminaires, so 9 in practice.
Offices 300–500 lx, classrooms 300, corridors 100, drawing work 750 (IS 3646).
8.33333333333333
Full answer, then cut to fewer decimals (not rounded):
- 8.33333333333333
- 8.3333333333333
- 8.333333333333
- 8.33333333333
- 8.3333333333
- 8.333333333
- 8.33333333
- 8.3333333
- 8.333333
- 8.33333
- 8.3333
- 8.333
- 8.33
- 8.3
- Luminaires to install (rounded up)
- 9
- Illuminance achieved with that number
- 324 lux
- Room index K = LW/(Hm(L + W))
- 2.02020202
Step-by-step solution
- N = E A / (F n UF MF) = 300 × 80 ÷ (3000 × 2 × 0.6 × 0.8) = 8.333333333
Lumen Method Formula
N = E A / (F n UF MF)
room index K = LW / (Hm(L + W))
Worked Example
A 10 × 8 m office lit to 300 lux with twin 3000 lm luminaires, UF 0.6 and MF 0.8:
- N = E A / (F n UF MF) = 300 × 80 ÷ (3000 × 2 × 0.6 × 0.8) = 8.333333333
Illuminance achieved with that number: 324 lux · Room index K = LW/(Hm(L + W)): 2.02020202
GATE tip
Round up to a number that fits a regular grid, then recheck the spacing-to-mounting-height ratio of the luminaire.
More Building Physics and Services Calculators
-
Reverberation Time Calculator
T₆₀ = 0.161 V / ΣSα
Eyring: T = 0.161 V / (−S ln(1 − ᾱ))
Example: A 1000 m³ hall with 200, 200 and 300 m² of surfaces at α = 0.02, 0.3 and 0.1: Reverberation time (Sabine) T₆₀ = 1.71277 s.
-
Air Changes per Hour Calculator
Q = ACH × V
Q in m³/h, V room volume in m³
Example: A 6 × 5 × 3 m room at 6 air changes per hour: Airflow = 540 m³/h.
-
Solar Angle Calculator
sin α = sin φ sin δ + cos φ cos δ cos h
δ = 23.45 sin(360(284 + n)/365); h = 15° × (t − 12)
Example: Latitude 23° N at solar noon on 21 June: Solar altitude α = 89.5502 °.
-
U-Value Calculator
U = 1 / (R_si + Σ d/λ + R_so)
R_si = 0.13, R_so = 0.04 m²·K/W for walls (ISO 6946)
Example: A 230 mm brick wall plastered 20 mm on both faces: U-value = 1.96268 W/(m²·K).
Frequently asked questions
What is the utilisation factor?
The fraction of lamp lumens that reaches the working plane, from manufacturer tables using the room index and reflectances.
What is the maintenance factor?
An allowance for dirt and lamp ageing, typically 0.7–0.8.
Sources
- The International System of Units (SI), 9th edition (SI Brochure), Bureau International des Poids et Mesures .
Last reviewed: . Factors are stored exactly and computed with 50-digit decimal arithmetic. See how we verify conversion factors.
Cite this page
APA
Scientific Converters. (2026, October 15). Lumen Method Calculator. Retrieved October 29, 2026, from https://scientificconverters.com/calculators/lumen-method-calculator/
IEEE
Scientific Converters, "Lumen Method Calculator," scientificconverters.com. Accessed: Oct. 29, 2026. [Online]. Available: https://scientificconverters.com/calculators/lumen-method-calculator/